• Home
  • Products
    • Power Transformer
    • Distribution Transformer
    • Dry Type Transformer
    • Ring Main Unit
    • Pad mounted Transformer
    • LV Switchgear
    • MV Switchgear
    • Current Transformer
  • Solutions
    • By Industry
  • Services
    • Services
  • Quality
    • System
    • Stardards
    • Q.C.
    • Certificates
    • After-sale Service
  • Companies
    • Profiles
    • Our Concept
    • Factories
    • Human Resources
    • Social Responsibility
    • Contact
Home > Products > GIS Switchgear

Products
  • Power Transformer
  • Distribution Transformer
  • Dry Type Transformer
  • Ring Main Unit
  • Pad mounted Transformer
  • LV Switchgear
  • MV Switchgear
  • Current Transformer
  • Voltage Transformer
  • Compact Substation
  • GIS Switchgear
  • AIS Switchgear
  • Disconnector
  • SF6 Circuit Breaker
11-33kV Gas Insulated Switchgear

Product Details

By reducing the number of components, utilizing modern materials correctly, we have developed an environmentally and user friendly product-SafeGear. Itis an air insulated (AIS), metal enclosed switchgear, and has same function with SM6.

SafeGearis a compact solution for a fully automated power distribution network. Supported by sensor technology and the latest in protection relays, it meets even the most demanding requirements in hospitals,airports, Utility, Power Plant, Industry, Windmills, Sports center, Metro, Shopping Center, residential quarters.



Technicaldata


Ratedvoltage

kV

12

24

36

BIL

- commonvalue

- acrosstheisolatingdistance


kV


75

85


125

145


170

195

ACwithstandvoltage

- commonvalue

- acrosstheisolatingdistance


kV


281)

321)


50

60


70

80

Ratedfrequency

Hz

50/60

50/60

50/60

Ratedcurrent



630/1250


630/1250


630/1250

-busbar

A

-feeder

A

630/1250

630/1250

630/1250

Ratedshort-timewithstandcurrent




25



25



25

-maincircuit

kA

-earthingcircuit

kA

25

25

25

Ratedpeakwithstandcurrent

kA

65

50

50

Rateddurationofshortcircuit

s

1

1

1

Arc-faultcurrent,1s

kA

20

20

16

Degreeofprotection,enclosure

IP2XC

IP2XC

IP2XC

Degreeofprotection,partitions

IP2X

IP2X

IP2X

Ambienttemperature



+40


+40


+40

-maximumvalue

[oC]

-maximumvalueof24h-mean


+35

+35

+35

-minimumvalue


-53)

-53)

-53)

Altitude above sea level

[m]

<10002)

<10002)

<10002)

1)   Higher values in accordance with national standards on request

2)   Adjustment is necessary for greater altitudes

3)   Lower ambient temperature on request.